Freeze protection fluid rules

SlimFit Series 2

What is going on

Only use freeze-prevention fluid approved by Weil-McLain. Automotive or standard glycol is never allowed. Flush any system that used glycol before fitting the boiler. Keep antifreeze at or below 50% by volume, because higher concentrations can cause sludge and heat exchanger damage. Test antifreeze and inhibitor levels at least once a year. If automatic fill is used with antifreeze, fit a water meter to track make-up water, since leaks can drop the freeze protection level before water is seen leaking.

Check in this order

  1. Flush the system before adding antifreeze.
  2. Confirm the fluid is a Weil-McLain approved product.
  3. Keep the concentration at or below 50% by volume.
  4. Test glycol concentration and inhibitor level at least annually and top up as needed.
  5. If automatic fill is used, install a water meter to monitor make-up water.

Applies to: SlimFit Series 2 boilers with freeze protection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.