Burner motor power supply, 240 VAC 1-phase in conduit

Vitotronic 100 GC1Vitotronic 300-K MW1S

What is going on

Power the burner motor from 240 VAC single phase using the factory-supplied cable and conduit.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect 240 VAC to terminals 21, 22 and 23 on the DIN rail in the connection enclosure. Fit a fuseable disconnect according to local codes.
  3. Connect the supplied power cable to the motor terminals on the burner.
  4. Plug the cable plug into the socket on the DIN rail in the connection enclosure.
  5. Check fuse and wire gauge sizing in the burner manual.

Applies to: Burners with 240 VAC, 1PH supply and connection in conduit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitotronic 300-K MW1S installation and service instructions, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.