Connecting Vitodens 200 WB2B with Vitotronic 200 HO1 to the Versatronik 300
What is going on
Boilers are daisy-chained from control to control with CAT5e cable using RJ45 ends (non-crossover). Plug the cable into the J1 receptacle in the upper right corner of the Versatronik 300 PCB. The cable can be made on site or ordered from Viessmann.
Check in this order
- Plug the CAT5e cable into the J1 receptacle at the upper right of the Versatronik 300 PCB.
- Daisy-chain the cable from control to control, using the LON communication boards on each boiler control.
- Connect the outdoor temperature sensor to the boiler. It can be mounted inside the boiler housing.
- Set the boiler LON and coding addresses as listed in the Vitodens 200 HO1 coding table.
- Make sure no two boiler controls share the same LON address.
Applies to: Vitodens 200 WB2B with Vitotronic 200 HO1
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control V1.4 manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.