Viessmann · Boiler troubleshooting
Cleaning the heating surfaces and combustion chamber
What is going on
Do not brush the heat exchanger. Scratches cause corrosion and brushing lodges deposits between coils. Discoloration is normal and does not affect function.
Likely causes
- Sediment or debris in the coil gaps
Check in this order
- Remove the burner assembly and reinstall it after service (see p. 50).
- Vacuum loose debris out of the combustion chamber.
- Rinse embedded sediment from the stainless steel heat exchanger with water or an approved cleaner such as Axiom Clean F Steel, following its instructions.
- Keep the refractory dry.
- If coil gaps are plugged, remove debris with the Viessmann tool (part 7858492, replacement blade 7840346) without scratching the surface.
- Flush the combustion chamber with water until it runs clear through the condensate trap.
- Clean out debris from the condensate trap and reinstall it.
- Cover electronic components with watertight material before cleaning.
- Never use a metal wire brush or powered brush.
Applies to: Stainless steel heat exchanger
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.