Installation completion checklist

I-Series Plus

What is going on

Every item must be answered YES before installation is complete. Any NO means the installation is not finished.

Check in this order

  1. Confirm the unit, vent and air intake meet clearance requirements.
  2. Remove corrosive compounds from around the combustion air intake and provide enough combustion air.
  3. Use the correct venting products for the model and verify the vent does not exceed maximum length. Install vent screens for Schedule 40 PVC/CPVC if needed.
  4. Purge the water lines of debris, clean the filter, and confirm hot and cold lines are not swapped.
  5. Confirm water supply pressure is adequate, free of chemicals, and below the hardness limit.
  6. Confirm the condensate drain is short, pitched down, corrosion resistant, protected from freezing, has an air gap, and is open to atmosphere.
  7. Confirm no external condensate trap is installed and the drain is not tied to the PRV or an AC coil drain.
  8. If a condensate pump is installed, wire it to shut off the boiler on failure.
  9. Confirm the PRV meets ANSI Z21.22 or CAN1-4.4, DHW PRV is rated to 150 PSI, heating PRV is rated to 30 PSI, and the discharge is piped per code.
  10. Confirm the gas system is sized correctly, the boiler is rated for the gas type, a gas leak test was done, a manual gas valve is installed, and inlet pressure is within limits.
  11. Confirm 120 VAC, 60 Hz on a properly grounded circuit with no extension cord or adapter.
  12. Prime the pump, fill to the specified pressure, and complete deaeration.

Applies to: I-Series Plus IP060160C

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 71-72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.