Beckett · Boiler troubleshooting
NX burner: Honeywell R7184 primary sequence and lockout
What is going on
Some NX burners use a Honeywell R7184 primary instead of the GeniSys 7505. Its timing is different.
Likely causes
- No flame within the 15 s trial for ignition
- Flame lost three times in a row
Check in this order
- Before any reset look in the chamber. If oil has pooled or the boiler is full of oil vapor, shut off power and oil, let it cool and clean it out first. Never try to relight a hot, vapor-filled chamber.
- On a call for heat the control does a 3 to 10 second safe-start check. If the burner does not start after that, the control may need its safety reset.
- Valve-on delay igniter and motor run 15 s before the oil valve opens.
- Trial for ignition flame must be proven within 15 s or the control locks out and must be reset by hand.
- Three lockouts in a row put it into restricted lockout.
- Once lit, the igniter stays on 10 s (or the whole run if wired for intermittent ignition).
- Flame lost while running 60 s recycle delay, then it tries again. Three flame losses in a row = lockout.
- Feature list R7184P has the diagnostic LED, cad cell indicator, valve-on delay and motor-off delay; R7184A/B have fewer features.
Applies to: Beckett NX burners with Honeywell R7184 primary on Weil-McLain Ultra Oil boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Figure 9 R7184P sequence of operation and control features p.14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.