Expansion tank piping, diaphragm vs closed type

SlimFit Series 2

What is going on

Size the expansion tank for the boiler and system water volume and temperature. An undersized tank lets system water blow out the relief valve and forces make-up water in, which can eventually fail the boiler.

Likely causes

  • Undersized expansion tank
  • Repeated make-up water addition through the fill valve

Check in this order

  1. Confirm the tank is sized for the total water volume and temperature, and check the boiler water content in the manual.
  2. Install the tank in the location shown in the manual or by recognized design methods.
  3. Connect the tank to the air separator only if the separator is on the pump suction side.
  4. Put the system fill connection at the same point as the tank connection to the system.
  5. For a diaphragm or bladder tank, pre-charge it to the system fill pressure before connecting. Install an automatic air vent on top of the air separator.
  6. If the boiler is above the main piping with a diaphragm tank, install an automatic air vent at the top of the outgoing boiler piping.
  7. For a closed-type tank, pitch horizontal piping up toward the tank 1 inch per 5 feet and connect with at least ¾-inch pipe.
  8. Do not install an automatic air vent on a closed-type tank system.

Applies to: SlimFit 1000-2000 Series 2 boilers with system expansion tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.