Weil-McLain · Boiler troubleshooting
Startup screen shows OUTDOOR: NOT ATTACHED
What is going on
The control reports that no outdoor temperature sensor is connected. An outdoor sensor is required by federal rules unless the system is exempt.
Likely causes
- Outdoor sensor not installed or not wired to the control
- System is exempt but the exemption was not set in the control
Check in this order
- Check whether the system meets one of the exemption conditions listed in the manual.
- If not exempt, install and wire the outdoor sensor.
- If exempt, answer YES on the exemption prompt and set ODT SENSOR EXEMPT to YES in BOILER SETTINGS.
- Only set exempt when the boiler really qualifies. Exempt units cannot use WWSD.
Applies to: Evergreen Series 2 boilers, startup and BOILER SETTINGS
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 65, 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.