Weil-McLain · Boiler troubleshooting

Startup screen shows OUTDOOR: NOT ATTACHED

Evergreen Series 2

What is going on

The control reports that no outdoor temperature sensor is connected. An outdoor sensor is required by federal rules unless the system is exempt.

Likely causes

  • Outdoor sensor not installed or not wired to the control
  • System is exempt but the exemption was not set in the control

Check in this order

  1. Check whether the system meets one of the exemption conditions listed in the manual.
  2. If not exempt, install and wire the outdoor sensor.
  3. If exempt, answer YES on the exemption prompt and set ODT SENSOR EXEMPT to YES in BOILER SETTINGS.
  4. Only set exempt when the boiler really qualifies. Exempt units cannot use WWSD.

Applies to: Evergreen Series 2 boilers, startup and BOILER SETTINGS

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Evergreen Series 2 advanced manual, p. 65, 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.