Viessmann · Boiler troubleshooting

Combustion fault through pulsation (no fault display)

Vitocrossal 200 CM2

What is going on

Burner pulsates or runs noisy, with no fault code shown.

Likely causes

  • Excessive gas input
  • Insufficient or excessive air
  • Condensate build-up in the flue system
  • Incorrect flue outlet
  • Thermo-acoustic or combustion noise
  • Incorrect CO2 settings

Check in this order

  1. Adjust gas input to the rated boiler heating output.
  2. Check the condensate drain.
  3. Check the flue outlet and flue system.
  4. Adjust the burner per p. 15.

Applies to: Vitocrossal 200 CM2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.