Viessmann · Boiler troubleshooting

Heating system design version 5: return temperature control with low loss header and three-way mixing valve

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Vitorond 200 boilers with Vitotronic 100 GC1, controlled by Vitocontrol-S VD2/CT3/CM2, with a low loss header and a three-way mixing valve. Sensor T1 closes the mixing valve in proportion to protect the boiler when the minimum return temperature is not reached. The temperature sensor in the low loss header controls the supply temperature. Used for older systems, systems in nurseries, or systems where hydraulic conditions are not clearly defined or downstream circuits cannot be controlled.

Check in this order

  1. Set the coding for system version 5 on every Vitotronic 100 GC1.
  2. Set the Vitocontrol-S coding as listed in the system version 5 coding table.
  3. Connect temperature sensor T1 to plug aJA.
  4. Size each boiler circuit pump so its volume supply is at least the maximum total heating circuit volume supply (recommendation: 110%).
  5. Check the connection diagram on site for completeness and function.

Applies to: Heating system design version 5

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 17-18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.