Remote modulation with a 0-10 VDC input (single boiler only)

SVF Series 1

What is going on

Use an external 0-10 VDC signal to modulate a single boiler. Not supported for boilers in a network. Using this input replaces Input 1 as the heat demand. The Unity control can use 0-10 VDC for either target operation or modulation, not both.

Check in this order

  1. Wire the 0-10 VDC positive signal to P15 terminal 6 and common to P15 terminal 5.
  2. Set the single-boiler Unity control configuration (not network).
  3. Put the system on Priority 2 and accept the Input 1 defaults in the Wizard.
  4. After the Wizard, go to Assign Inputs, select Input 1, and change SOURCE from TT1 to 0-10V.
  5. If DHW is needed, wire the DHW aquastat to Input 2 or 3 and assign that input to Priority 1.
  6. Wire the system pump to Output 1 (120VAC). Output 1 follows the heat demand.

Applies to: SVF 1500-3000 Series 1 with Unity control, single boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.