Weil-McLain · Boiler troubleshooting
Remote modulation with a 0-10 VDC input (single boiler only)
What is going on
Use an external 0-10 VDC signal to modulate a single boiler. Not supported for boilers in a network. Using this input replaces Input 1 as the heat demand. The Unity control can use 0-10 VDC for either target operation or modulation, not both.
Check in this order
- Wire the 0-10 VDC positive signal to P15 terminal 6 and common to P15 terminal 5.
- Set the single-boiler Unity control configuration (not network).
- Put the system on Priority 2 and accept the Input 1 defaults in the Wizard.
- After the Wizard, go to Assign Inputs, select Input 1, and change SOURCE from TT1 to 0-10V.
- If DHW is needed, wire the DHW aquastat to Input 2 or 3 and assign that input to Priority 1.
- Wire the system pump to Output 1 (120VAC). Output 1 follows the heat demand.
Applies to: SVF 1500-3000 Series 1 with Unity control, single boiler
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.