Hydrostatic pressure test before piping

CGi Series 5

What is going on

Test the boiler water side before water, gas or electrical hookup. Test pressure limits depend on the relief valve rating.

Check in this order

  1. Remove the shipping nipple from the supply tapping and remove the relief valve. Plug the relief tapping with a 3/4 inch NPT plug.
  2. Install the drain valve and pressure/temperature gauge on the return and supply connections, plus the circulator hardware.
  3. Connect a hose from the boiler drain valve to a fresh water supply.
  4. Install shutoff valves with nipples on the system supply and return to bleed air during fill.
  5. Open the shutoff valves, then slowly open the drain valve and fill the boiler with water.
  6. When water flows from the shutoff valves, close the drain valve and then close the shutoff valves.
  7. Slowly raise pressure to the limit in the pressure table, and hold for no more than 10 minutes.
  8. Keep constant pressure during the test and check all joints for leaks. Repair any leak right away.
  9. Disconnect the fill hose, drain the boiler, remove test nipples and valves not used in the system, and reinstall the relief valve.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.