Viessmann · Boiler troubleshooting

Piping the boiler for heating/cooling (chilled water) use

Vitocrossal 300 CA3B Dual Fuel

What is going on

When the boiler works with a chiller, the chilled medium must be piped in parallel with the boiler using valves that keep chilled water out of the boiler. Flow control valves or other automatic means must stop gravity circulation of boiler water during cooling. The circulating pump must run from a separate on/off switch, not from the boiler control. Metal tags should identify the seasonal valves.

Likely causes

  • Gravity circulation of boiler water during the cooling cycle.

Check in this order

  1. Pipe the chilled medium in parallel with the boiler.
  2. Fit valves V1 and V2 and tag them with metal tags.
  3. Fit flow control valves or other automatic means to stop gravity circulation.
  4. Power the circulating pump from a separate on/off switch, not from the boiler control.
  5. Check the chiller manufacturer's requirements.

Applies to: Vitocrossal 300 CA3B Dual Fuel in heating/cooling applications

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.