System Example 01: cascade control for modulating boilers

Versatronik 200

What is going on

Cascade controller for modulating OT boilers 1 to 8. The boiler set point comes from the heating system manager and the boiler modulates to reach it. Outdoor reset with outdoor sensor and common supply sensor. No low loss header or hydraulic separator, though closely spaced tees are possible. No DHW production, no DHW recirculation pump and no space heating control. Individual boiler pumps are run from the boiler pump output.

Check in this order

  1. Wire outdoor sensor to terminal 1 and common supply sensor to terminal 2.
  2. Connect the CAN BUS H, L, -, + terminals to the Coco OT modules.
  3. Set the system selection to 01 during start-up.

Applies to: Cascade of modulating OT boilers, no DHW

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 21-22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.