Viessmann · Boiler troubleshooting

System layout with multiple heating circuits, mixing valves and low-loss header

Vitodens 200-W

What is going on

Piping layout for a DHW storage tank, a low-loss header, several mixing-valve heating circuits and one circuit without a mixing valve. Contact the Viessmann sales representative for help with the design.

Check in this order

  1. Locate the expansion tank as shown in the layout.
  2. Make sure the boiler pump and the heating circuit pumps pump into the boiler as illustrated.
  3. Use the accessory kit for each heating circuit with a mixing valve.
  4. Fit the temperature sensor for the low-loss header as shown.
  5. Use the Vitotronic 200-H, HK1B mixing valve control with LON module if it replaces the accessory kit and Vitocontrol.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA 80 to 100, 285 to 352 installation manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.