Hydronic piping requirements for applications

NCB700

What is going on

These diagrams show the piping concept only. Local codes, building codes and the expansion tank sizing in the manual take priority. Air must be able to leave the system, so vents and purgers must be placed where air collects. Air elimination devices work best when located high in the system, near the fill point and expansion tank, where pressure is positive.

Check in this order

  1. Use straight pipe with at least 1/2 in (12 mm) inside diameter upstream of all pumps.
  2. Size the expansion tank according to the manual's expansion tank instructions.
  3. Install an air separator or air vent to remove air from the system water.
  4. Install a NaviClean strainer in the system return to catch debris (recommended).
  5. Use pumps with built-in check valves, or install a check valve on each pump outlet.
  6. Follow local rules. In Massachusetts, install a vent in the cold water line per 248 CMR. New Jersey has similar requirements.
  7. Refer to the fill connection section for make-up water connection details.

Applies to: NCB700 hydronic piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 195, 198-199. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.