Weil-McLain · Boiler troubleshooting
Adjust system bypass valves (primary/secondary bypass)
What is going on
Used for high water content, radiant or low-return-temperature systems. Adjust valves to raise return water temperature to the boiler.
Likely causes
- Low return water temperature causing flue gas condensation and corrosion
Check in this order
- Start with valve 2 fully closed and valve 1 fully open.
- Slowly open valve 2 while closing valve 1.
- Adjust both valves until the boiler pressure/temperature gauge reads 160°F or higher.
- Pause between adjustments so temperatures can level off, since boiler water temperature rises slowly as flow changes.
Applies to: System bypass method, Figure 19
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.