Adjust system bypass valves (primary/secondary bypass)

EG / PEG Series 7

What is going on

Used for high water content, radiant or low-return-temperature systems. Adjust valves to raise return water temperature to the boiler.

Likely causes

  • Low return water temperature causing flue gas condensation and corrosion

Check in this order

  1. Start with valve 2 fully closed and valve 1 fully open.
  2. Slowly open valve 2 while closing valve 1.
  3. Adjust both valves until the boiler pressure/temperature gauge reads 160°F or higher.
  4. Pause between adjustments so temperatures can level off, since boiler water temperature rises slowly as flow changes.

Applies to: System bypass method, Figure 19

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.