Domestic hot water plumbing connections

I-Series Plus

What is going on

DHW piping and components must be approved for potable water. Water connections must follow state and local plumbing codes. An approved pressure relief valve is required and must be accessible for service.

Likely causes

  • Debris in the water line will damage the boiler
  • Non-potable piping or boiler water treatment chemicals contaminate the DHW supply

Check in this order

  1. Purge the water line of all debris and air before connecting.
  2. Do not connect the DHW to any piping previously used with a non-potable water heater.
  3. Do not introduce boiler water treatment or toxic chemicals into the DHW or potable piping.
  4. Confirm the water filter on the boiler is clean and installed.
  5. Connect the cold water supply to the DHW cold inlet connection on the bottom of the boiler, with an isolation valve.
  6. Connect the hot water supply to the DHW hot outlet connection on the bottom of the boiler, with an isolation valve.
  7. Install the DHW pressure relief valve per ANSI Z21.13 and ASME Section IV and keep it accessible.

Applies to: DHW side plumbing

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation manual, p. 51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.