Viessmann · Boiler troubleshooting

Rooms cold while the burner is running

Vitotronic 300

What is going on

The burner runs but the rooms stay cold, even with a low outdoor temperature.

Likely causes

  • Time incorrectly set
  • Heating program w or 9 selected
  • DHW priority active on a tank system
  • On/off switch on the mixing valve motor is OFF
  • Heating curve setting incorrect
  • Control unit incorrectly programmed

Check in this order

  1. Set the correct time on page 20.
  2. Set heating program rw (page 6) if program w or 9 is selected.
  3. On tank systems, wait until the DHW tank heats up (w goes off in the display).
  4. Turn the mixing valve motor on/off switch to I ON.
  5. Check and correct the heating curve on page 21.
  6. Check and correct the temperature settings (page 8), time program (page 12) and heating program (page 7).

Applies to: Room heating

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 operating instructions, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.