Viessmann · Boiler troubleshooting
Check neutralization unit (if fitted)
What is going on
Granulate is consumed as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is required.
Likely causes
- Condensate pH below 6.5
- Granulate used up
Check in this order
- Check condensate pH with a pH strip.
- If pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Add granulate up to the marked level.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.