Viessmann · Boiler troubleshooting

Check neutralization unit (if fitted)

Vitodens 200-W B2HA

What is going on

Granulate is consumed as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is required.

Likely causes

  • Condensate pH below 6.5
  • Granulate used up

Check in this order

  1. Check condensate pH with a pH strip.
  2. If pH is below 6.5, replace the granulate.
  3. If the unit is contaminated, rinse it with tap water.
  4. Add granulate up to the marked level.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.