Viessmann · Boiler troubleshooting
Category I venting requirements (natural gas or propane)
What is going on
Category I venting is the standard option for this boiler on gas. Use Type B or Type L vent for the whole run where possible. B-vent is not allowed on #2 oil.
Likely causes
- Down draft or condensation in the vent
Check in this order
- Use approved vent material only. Do not connect the vent to any mechanical draft system under positive pressure.
- Put the boiler as close to the chimney as possible, with the shortest run and fewest elbows. Avoid long horizontal runs.
- Support horizontal runs so they do not sag. Give them at least 1/4 in. (6 mm) rise per ft. from the boiler to the terminal. Strap every 4 ft. (1.2 m).
- Insulate the vent pipe.
- Terminate outside at least 6 ft. (1.8 m) above the boiler. Extend the vent at least 3 ft. (91 cm) above the roof penetration.
- Make sure the termination is at least 2 ft. (61 cm) above any building part within 10 ft. (3 m) horizontal and at least 2 ft. (61 cm) above roof peaks within 10 ft. (3 m).
- Correct any down draft or condensation problems.
- Install a stainless steel liner in masonry or unlined chimneys where recommended.
- With B-vent on natural gas or LP, measure stack temperature before dilution air. It must not exceed 480 F (249 C).
- Follow local codes.
Applies to: Vitorond 200 VD2 Category I (natural gas, liquid propane)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.