Category I venting requirements (natural gas or propane)

Vitorond 200 VD2

What is going on

Category I venting is the standard option for this boiler on gas. Use Type B or Type L vent for the whole run where possible. B-vent is not allowed on #2 oil.

Likely causes

  • Down draft or condensation in the vent

Check in this order

  1. Use approved vent material only. Do not connect the vent to any mechanical draft system under positive pressure.
  2. Put the boiler as close to the chimney as possible, with the shortest run and fewest elbows. Avoid long horizontal runs.
  3. Support horizontal runs so they do not sag. Give them at least 1/4 in. (6 mm) rise per ft. from the boiler to the terminal. Strap every 4 ft. (1.2 m).
  4. Insulate the vent pipe.
  5. Terminate outside at least 6 ft. (1.8 m) above the boiler. Extend the vent at least 3 ft. (91 cm) above the roof penetration.
  6. Make sure the termination is at least 2 ft. (61 cm) above any building part within 10 ft. (3 m) horizontal and at least 2 ft. (61 cm) above roof peaks within 10 ft. (3 m).
  7. Correct any down draft or condensation problems.
  8. Install a stainless steel liner in masonry or unlined chimneys where recommended.
  9. With B-vent on natural gas or LP, measure stack temperature before dilution air. It must not exceed 480 F (249 C).
  10. Follow local codes.

Applies to: Vitorond 200 VD2 Category I (natural gas, liquid propane)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.