Weil-McLain · Boiler troubleshooting
Check the high flue pressure switch
What is going on
Confirms the high flue pressure switch trips and the control locks out as expected.
Check in this order
- Check that the switch wire connections are secure and the tubes are tight on the pressure ports.
- Inspect the tubes for damage or debris and replace if needed.
- After checking control settings, disconnect the tube at the condensate dish.
- Gently blow into the tube until the high flue pressure switch opens and the control shows a lockout.
- Clear the lockout on the control and confirm it does not come back.
- Reconnect the tube securely to the condensate dish.
Applies to: SVF 500/600 boilers, flue pressure switch
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.