Weil-McLain · Boiler troubleshooting

Check the high flue pressure switch

SVF 500/600 Series 1

What is going on

Confirms the high flue pressure switch trips and the control locks out as expected.

Check in this order

  1. Check that the switch wire connections are secure and the tubes are tight on the pressure ports.
  2. Inspect the tubes for damage or debris and replace if needed.
  3. After checking control settings, disconnect the tube at the condensate dish.
  4. Gently blow into the tube until the high flue pressure switch opens and the control shows a lockout.
  5. Clear the lockout on the control and confirm it does not come back.
  6. Reconnect the tube securely to the condensate dish.

Applies to: SVF 500/600 boilers, flue pressure switch

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.