Viessmann · Boiler troubleshooting
Gas connection and piping installation
What is going on
Gas piping must be sized for the whole residence. Install the shutoff and drip leg before the boiler and make the gas connection at the 1 in. NPT boiler inlet.
Check in this order
- Size the gas pipe from length, number of fittings, gas type and the maximum input of all gas appliances in the residence.
- Confirm no noticeable gas pressure drop occurs when any unit lights or runs.
- Do not exceed a maximum gas supply pressure of 14 in. w.c.
- Before connecting, install a ground joint union, a capped drip leg and a manual equipment shutoff valve. Use valves listed by a nationally recognized testing agency.
- Make the boiler gas connection (1 in. NPT).
- Tag the shutoff valves and show the operator where they are.
- Where the boiler runs on LPG in rooms below grade, install an external safety solenoid valve. Refer to the Service Instructions for system coding.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 18-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.