Replacing the display and programming unit or coding card

Vitocrossal 300 CA3B Dual Fuel

What is going on

Access the burner control interface and swap the coding card or display unit.

Check in this order

  1. Disconnect the KM-BUS connector.
  2. Undo the 2 mounting screws. Tighten to 9 lb.in (1 Nm).
  3. Lift the display and programming unit and unplug the burner control unit connecting cable.
  4. Remove the display and programming unit.
  5. To change the coding card, pull it from the burner control unit and insert the new card.
  6. Install the new display and programming unit in reverse order.

Applies to: CA3B Dual Fuel 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.