Weil-McLain · Boiler troubleshooting
Outdoor reset operation (supply temperature follows outdoor temperature)
What is going on
Target supply temperature is set between Supply Min and Supply Max across an outdoor reset band.
Check in this order
- Set the desired supply temperatures for each space heating zone in its priority menu.
- Set Supply Max to the required supply water temperature at design maximum heat loss. Typical is 180°F for finned tube baseboard.
- Set Supply Min to the minimum desired supply water temperature. It can be set as low as 70°F.
- Set OD Reset Max to the outdoor temperature where the target reaches Supply Min. The factory default is 70°F.
- Set OD Reset Min to the outdoor temperature where the target reaches Supply Max. Set it equal to the outdoor design temperature (ODT) for the site. The factory default is 0°F.
Applies to: SlimFit Series 3 Control with outdoor sensor
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SlimFit Series 3 boiler manual, p. 68. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.