Viessmann · Boiler troubleshooting
Checking the boiler temperature sensor
What is going on
Resistance check of the boiler temperature sensor against the curve in the manual.
Likely causes
- Faulty boiler temperature sensor
Check in this order
- Pull the plug and measure the sensor resistance.
- Compare the reading with the curve.
- Replace the sensor if the deviation is severe.
- Release the strain relief on the sensor well and pull the sensor out of the well, then disconnect the plug.
- Install the new sensor in reverse order.
Applies to: Vitocrossal 300 CU3A 26 to 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.