Initial BACnet/IP gateway configuration

Versatronik 505 NR2/BACIPVersatronik 505D NR2/BACIP

What is going on

Connect a laptop directly to the gateway on an isolated network, then open the configuration pages in a browser.

Check in this order

  1. Connect the computer directly to the gateway BACnet interface with no other devices attached.
  2. Set the computer to automatic IP (DHCP), or set its IP to 192.168.88.90 with subnet mask 255.255.255.0.
  3. Cycle the gateway power off and on.
  4. Open a browser and go to the gateway configuration address 192.168.88.89/admin.
  5. Log in with the default admin/admin, or the password you changed, then change it on the Change Password screen if needed.
  6. Set the BACnet Device Settings. Give the Device ID a value that is unique on the whole BACnet network.
  7. Press SAVE on every screen where you changed something.
  8. Confirm Activate Configuration and save. The gateway stores the settings and reboots.
  9. Record all changes, as the gateway pages can be reached via 192.168.88.89 and the address you set.

Applies to: Versatronik 505 NR2/BACIP and 505D NR2/BACIP gateways

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 505 and 505D BACnet IP manual, p. 18-19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.