Viessmann · Boiler troubleshooting
Clearances to combustibles and service space
What is going on
The boiler is listed for zero clearance to combustibles when vented with an approved single-wall special venting system (AL-29-4C) or UL/ULC-listed CPVC/PPs vent. This supersedes the clearance on the venting label. The approved installation clearances include closet and alcove mounting. Keep 12 in. (305 mm) on the side for viewing the rating plate and fitting the PRV kit. If the PRV is rotated 90° forward with an extension, the side clearance can be reduced to a smaller value (the exact figure is unreadable in this copy). The reduced value is only needed to remove the front cover and read the rating plate. Keep the gas ignition components protected from spray and splashing.
Check in this order
- Use the venting listed for zero-clearance installation, or follow the venting system label clearances if not using that system.
- Leave at least 12 in. (305 mm) at the side for service and PRV kit fitting, unless the PRV extension is used.
- Keep the ignition components protected from water spray or splashing during operation and service.
- Refer to the Venting System Installation Instructions for details.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA installation instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.