Gas valve throttle screw and offset adjustment
What is going on
Only for a qualified technician with calibrated combustion instruments. Adjust only when combustion tests call for it. Gas valve outlet pressure is factory set and must not be measured or adjusted in the field.
Likely causes
- High or low fire CO2 outside the Figure 73 range
- Difficulty igniting
- Poor flame stability at low fire
- Combustion noise
- High carbon monoxide readings
Check in this order
- Force the firing rate to High in Manual test mode and wait for high fire RPM to settle.
- Read CO2. Remove the blue cover on the throttle screw opening.
- If CO2 is high, turn the throttle screw clockwise in small 1/8-turn steps to lower input.
- If CO2 is low, turn the throttle screw counterclockwise in small 1/8-turn steps to raise input.
- Reinstall the blue cover.
- Lock the boiler at low fire and confirm the low fire RPM is correct.
- If low fire is not acceptable, remove the offset cover screw and use a T40 Torx driver. Turn clockwise to raise CO2 and counterclockwise to lower it.
- Reinstall the cover screw, then return the boiler to AUTO and recheck high fire.
- If both fires cannot be brought into range, contact the WM Technologies representative.
Applies to: SlimFit SF-550 and SF-750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 boiler manual, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.