Viessmann · Boiler troubleshooting

Checking DHW, supply and room temperature sensors

Vitocrossal 300 CA3B Dual Fuel

What is going on

Check NTC 10 kΩ sensors by resistance against the curve. The supply sensor can be used as contact or immersion sensor.

Likely causes

  • Sensor resistance far from curve
  • Poor sensor installation

Check in this order

  1. Pull the corresponding plug.
  2. Measure the sensor resistance and compare it with the NTC 10 kΩ curve.
  3. If the deviation is severe, check the installation and replace the sensor if required.
  4. See the Vitotrol 300 installation and service instructions for more detail.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 76. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.