Viessmann · Boiler troubleshooting

Boiler does not fire although the control calls for heat

Versatronik 300 Cascade Control

What is going on

The Versatronik 300 can demand the exhaust or damper device without the boilers firing. If the boiler water temperature is already above its actual operating set point, the boiler will not fire.

Likely causes

  • Boiler temperature above its operating set point
  • Combustion air or exhaust device operating without boiler demand

Check in this order

  1. Check that the boiler temperature is below its operating set point.
  2. Confirm the combustion air feedback signal reaches the INT input.
  3. Confirm the override function is not forcing the boilers on without the combustion air demand signal on Vitodens systems.

Applies to: Versatronik 300 cascade with Vitodens systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control V1.4 manual, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.