Domestic hot water relief valve installation

NCB700

What is going on

Install an approved 3/4 in domestic hot water relief valve with a maximum pressure rating of 150 psi on the DHW outlet. No separate high-limit safety device is needed because the boiler has an integrated over-temperature switch, but local code may require one.

Check in this order

  1. Install one 3/4 in DHW relief valve rated for 150 psi maximum on the DHW outlet
  2. Install the valve as close to the boiler as possible with no other valve between them
  3. Check that the valve's discharge capacity is at least the boiler's maximum DHW pressure rating
  4. Check that the valve's BTU/H rating is at least the boiler's maximum input
  5. Run the discharge pipe so hot water cannot spray people or equipment
  6. Terminate the discharge 50 to 150 mm (2 to 6 in) above the floor or floor drain
  7. Keep the discharge line free of reducers or restrictions and do not plug the valve
  8. Check local code for any added temperature limiting device

Applies to: NCB700 domestic hot water circuit

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 188-190. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.