Viessmann · Boiler troubleshooting

Check and replace burner refractory, cylinder burner and fan flapper

Vitodens 200-W B2HA

What is going on

Inspect the burner refractory and cylinder burner, and clean or replace the flue gas flapper.

Check in this order

  1. Remove the electrode block and ionization electrode A.
  2. Undo the three retaining clips B and remove the refractory ring C.
  3. Loosen the four Torx screws D and remove the cylinder burner assembly E and gasket F.
  4. Fit a new cylinder burner assembly and gasket, and tighten the screws to the torque in the torque table.
  5. Refit the refractory ring and clips, then the electrode block and ionization electrode.
  6. To check the flue gas flapper undo three screws and remove fan A, remove flapper B, check flapper and gasket for dirt or damage, refit flapper and fan.

Applies to: Vitodens 200-W B2HA 45, 60

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.