Viessmann · Boiler troubleshooting
Annual heating technician service checks
What is going on
Annual inspection and test list for the heating technician. Combustion test must be done by a qualified heating technician.
Check in this order
- Test functionality of the safety high limits.
- Test and establish correct chemical makeup of the system water.
- Check the flue pipe, chimney connection and chimney.
- Check the pressure relief valve and system pressure and confirm proper operation.
- Check heating pipe joints, valves and air vents. Correct leaks immediately and find the cause of any defect.
- Check combustion air supply and ventilation to the boiler and mechanical room.
- Test high limits by dialing lower settings, then switching burners on and off to verify function.
- Test low water cut-off and verify it per the manufacturer instructions.
- Check maintenance or lubrication requirements for the circulation pumps.
- Check gas-tight connection of gas piping, unions, gas valve and manifold.
- Check proper ignition of the burners.
- Perform the combustion test.
Applies to: Vitocrossal 200 CI2, all sizes
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 98. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.