Low temperature systems: choose the piping method

CGi Series 5

What is going on

For radiant or converted gravity systems, primary/secondary piping is preferred because it keeps the heating circuit flow independent of boiler bypass adjustment. Other options are boiler bypass (Figures 21 and 22) and system bypass (Figure 23). System bypass does not control radiant supply temperature, so it is not used for radiant systems.

Likely causes

  • Return water below 130°F causing corrosion of sections or burners

Check in this order

  1. Use primary/secondary piping (Figure 19 or 20) when possible.
  2. If primary/secondary cannot be used, use boiler bypass piping (Figure 21 or 22).
  3. Use system bypass (Figure 23) only for converted gravity systems where reduced flow will not cause heat distribution problems.
  4. Do not use system bypass for radiant systems.
  5. If radiant tubing has no oxygen barrier, use a heat exchanger.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 30-31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.