Weil-McLain · Boiler troubleshooting

No display and nothing operating

Ultra Series 4

What is going on

Control is not getting 120 V power.

Likely causes

  • Service switch or breaker off
  • No 120 V supply
  • Boiler ON/OFF power switch behind the control pod off
  • Blown 12 A line voltage fuse
  • Wiring fault inside the control pod

Check in this order

  1. Confirm the service switch and/or circuit breaker is on.
  2. Check for 120 V at the service switch; if none, fix the supply.
  3. Turn on the Ultra power switch behind the control pod.
  4. Check for 120 V at the line voltage terminal block inside the control pod; correct the wiring per the diagram if needed.
  5. Inspect the 12 A fuse (page 116) and replace it with the proper part if blown. If it blows again, recheck wiring.

Applies to: Ultra 80, 105, 155, 230, 299, 399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 gas-fired water boiler manual, p. 119. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.