Viessmann · Boiler troubleshooting
Fixed high limit test
What is going on
Field test of each boiler section's fixed high limit. Per CSD-1, the test is done where required by law. Viessmann is not responsible for damage caused by overheating during this test.
Check in this order
- Use the emission test switch on each boiler section to call for heat.
- In menu 6 of each burner control (GC310), set item 4 (maximum boiler water temperature) to 243°F (117°C) so it is above the fixed high limit. For a reduced-temperature test, set a lower value such as 122°F (50°C).
- Activate the emission test switch on the section. The burner starts.
- Slowly throttle the water flow to the boiler.
- Watch the temperature on the GW6C service display.
- When the fixed high limit is reached, the burner control hard locks out with F F2 displayed. The fan runs for 10 minutes. Reset only after the water temperature drops.
- Restore the original menu 6 item 4 setting when the test is finished.
Applies to: Each boiler section, burner control GC310
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B service instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.