Viessmann · Boiler troubleshooting

Fixed high limit test

Vitocrossal 300 CA3B

What is going on

Field test of each boiler section's fixed high limit. Per CSD-1, the test is done where required by law. Viessmann is not responsible for damage caused by overheating during this test.

Check in this order

  1. Use the emission test switch on each boiler section to call for heat.
  2. In menu 6 of each burner control (GC310), set item 4 (maximum boiler water temperature) to 243°F (117°C) so it is above the fixed high limit. For a reduced-temperature test, set a lower value such as 122°F (50°C).
  3. Activate the emission test switch on the section. The burner starts.
  4. Slowly throttle the water flow to the boiler.
  5. Watch the temperature on the GW6C service display.
  6. When the fixed high limit is reached, the burner control hard locks out with F F2 displayed. The fan runs for 10 minutes. Reset only after the water temperature drops.
  7. Restore the original menu 6 item 4 setting when the test is finished.

Applies to: Each boiler section, burner control GC310

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.