Viessmann · Boiler troubleshooting

External control: switch on 2nd stage burner

Vitotronic 100GC1

What is going on

Dry contact at plug aVD starts the second burner stage.

Check in this order

  1. Connect a dry contact to terminals 2 and 3 of plug aVD.
  2. Contact closed both burner stages run.
  3. Contact open both stages stop.
  4. 2nd stage switches off 2 K sooner than the 1st stage.

Applies to: Two-stage burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100, GC1 installation manual, p. 60. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.