System layout 3: DHW storage tank with closely spaced tees
What is going on
Layout with DHW storage tank and one heating circuit using closely spaced tees instead of a low-loss header. Viessmann prefers a low-loss header.
Check in this order
- Install closely spaced tees at 4 times the pipe diameter or 12 in (305 mm) apart.
- Install the primary pump so it pumps into the boiler.
- Install the external boiler/DHW controller and DHW tank aquastat or sensor.
- Install the air vent, PRV, TPV and expansion tank as shown.
Applies to: Vitodens 100-W WB1B 26 and 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service Instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.