Navien · Boiler troubleshooting
Wiring a 3-zone zone pump system
What is going on
Dry contact zone pumps, with or without 24 VAC thermostat power, plus optional DHW recirculation.
Check in this order
- Wire each zone pump's line and neutral to its own zone pump terminal on the boiler (zone pumps 1 to 3, each max. 2.5 A).
- Connect the boiler external pump to its terminal if one is used (max. 2.5 A). The boiler internal pump uses its own terminal.
- For a 24 V thermostat, connect it to the R and C terminals on the boiler PCB. Use C only when the thermostat has a COMMON wire.
- For thermostats with their own 24 VAC power, wire the thermostat input, 24 VAC neutral and 24 VAC line to each thermostat input.
- For DHW recirculation, use a recirculation timer, aquastat or HotButton push button, and select external recirculation in the DHW recirculation menu.
- For combi pre-heat, skip the recirculation pump and select combi pre-heat in the DHW recirculation menu.
- If the DHW recirculation menu is set to Always On, Intelligent or Weekly, no aquastat or extra HotButton is needed.
Applies to: NCB700 zone pump systems
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 40, 41, 42, 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.