Wiring a 3-zone zone pump system

NCB700

What is going on

Dry contact zone pumps, with or without 24 VAC thermostat power, plus optional DHW recirculation.

Check in this order

  1. Wire each zone pump's line and neutral to its own zone pump terminal on the boiler (zone pumps 1 to 3, each max. 2.5 A).
  2. Connect the boiler external pump to its terminal if one is used (max. 2.5 A). The boiler internal pump uses its own terminal.
  3. For a 24 V thermostat, connect it to the R and C terminals on the boiler PCB. Use C only when the thermostat has a COMMON wire.
  4. For thermostats with their own 24 VAC power, wire the thermostat input, 24 VAC neutral and 24 VAC line to each thermostat input.
  5. For DHW recirculation, use a recirculation timer, aquastat or HotButton push button, and select external recirculation in the DHW recirculation menu.
  6. For combi pre-heat, skip the recirculation pump and select combi pre-heat in the DHW recirculation menu.
  7. If the DHW recirculation menu is set to Always On, Intelligent or Weekly, no aquastat or extra HotButton is needed.

Applies to: NCB700 zone pump systems

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 40, 41, 42, 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.