Weil-McLain · Boiler troubleshooting

Setting the flue collector hood, rear base and drawer assembly

EGPEG

What is going on

On PEG boilers the flue collector hood and rear base panels come factory installed. A gas-tight seal is required at the hood and base panels to prevent flue gas spillage. On EG boilers the front base panel, burner drawer and manifold are assembled and set into the section assembly.

Likely causes

  • Broken gas-tight seal causing flue gas spillage and carbon monoxide
  • Burners not seated in the back burner support slots, or orifices not centered over the burners
  • Wrong orifice size for the input rating

Check in this order

  1. Set the flue collector hood as shown and seal it with the boiler cement furnished.
  2. Fasten the rear base panel channel to the section assembly and seal along the top of the insulation panels with boiler cement (EG 30 through 75).
  3. Fasten the front base panel (6 1/8 in high) and the rear base channel to the section assembly, sealing along the top of the insulation panels.
  4. Verify the orifices against the orifice sizing table before installing.
  5. Place burners in the drawer so they sit in the slots of the back burner support with openings facing up.
  6. Slide the drawer under the front base panel and attach it to the section assembly.
  7. Level and straighten the burners so each gas orifice injects down the center of its burner.

Applies to: EG and PEG boilers, burner drawer and base assembly

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, pp. 15-16 (see Table 5 and Figures 8-11 on p. 17). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.