Gas fireplace troubleshooting guides
70 guides. Troubleshooting guides for gas fireplace equipment. Each one lists the likely causes and what to check, in order.
All brands (8)
- Flameworks millivolt valve: pilot outage or burner will not come on
Fireplace or heater with a Flameworks millivolt or 3 V gas valve: pilot will not stay lit, or the main burner will not come on. - Maxitrol GV60 remote valve: fireplace will not light or respond
Fireplace with a Maxitrol GV60 battery-powered remote valve: no response, beeping, pilot or burner problems. - Proflame (SIT DFC): fan, AUX outlet, split flow or OFF command not working
Proflame GT system with Fan Control Module: fan or AUX outlet not responding, split-flow burner not switching, or the fireplace will not shut off from - Proflame (SIT DFC): pilot lights but main burner will not light or drops out
Proflame system: pilot proves but the main burner will not come on, will not stay on, or does not modulate. - Proflame (SIT DFC): pilot will not light or DFC locks out
Fireplace with SIT Proflame electronic ignition (DFC board, 880/885/886 valve, GT remote): no pilot, or the DFC goes into lockout. - SIT 820 Nova millivolt valve: main burner will not come on or will not cycle
Pilot is fine but the burner will not light with the switch/thermostat, lights intermittently, or the flame looks wrong. - SIT 820 Nova millivolt valve: pilot will not light
Standing-pilot fireplace with an SIT 820 Nova millivolt valve: no pilot. - SIT 820 Nova millivolt valve: pilot will not stay lit
The pilot lights while the knob is held but goes out when released, or drops out later.
Heat & Glo (7)
- DSI fireplace: burner lights but will not stay lit
The burner lights and then goes out because the module does not prove flame (flame rectification). - DSI fireplace: ignitor sparks but burner will not light
Spark is present but the burner never lights; on RAM 1MC1 modules it sparks for 4 s (-01) or 7 s (-05) then locks out. - DSI fireplace: ignitor will not spark
Heat-N-Glo direct spark ignition fireplace: no spark at the electrode when the fireplace is switched on. - Fireplace with PVK-80 power vent: flames lifting or jumping
Flame tuning on a Heat-N-Glo DSI fireplace with the PVK-80 power vent; also covers the short delay before ignition. - HSI fireplace: flame comes on but will not stay lit
Before you start, make sure the gas is off and the unit is cool, and turn the power off before opening any junction box. On a Heat-N-Glo hot surface i - HSI fireplace: hot surface ignitor will not glow
Heat-N-Glo hot surface ignition fireplace: the ignitor does not heat up. It will not glow without 24 VAC on the 24 V side of the module. - HSI fireplace: ignitor glows but no flame
The hot surface ignitor heats up but the burner does not light.
Lennox (3)
- Fireplace does not respond to the remote - Lennox Elite LDV
Remote not working on the Elite Linear View? Nine times out of ten it's batteries or the little slider on the wall receiver. Start there before you go - First start-up: pilot slow to light - Lennox Elite LDV
New install, first start, pilot won't catch right away. Usually not a fault. The new gas line is full of air, and the Elite LDV control will keep tryi - Sooting or flame too blue - Lennox Elite LDV
Long orange flames with black tips and soot on the glass or near the vent cap, or flames that stay blue and see-through.
Majestic (12)
- Blue, lifting flame (ghosting)
A blue flame that lifts off the burner on a Majestic DVBL7 is called ghosting. It is a sign that the unit is not getting enough combustion air, which - Glass sooting
Black soot on the glass or logs of your Majestic DVBL7 usually means the flame is touching something it shouldn't, most often the logs. That's an inco - Millivolt: frequent pilot outages
The pilot on your Majestic DVBL7 millivolt fireplace keeps going out. Before you relight it again, turn the gas control off and let any gas clear for - Millivolt: pilot lights but will not stay lit
The pilot lights on the Majestic DVBL7 millivolt unit but drops out when you let go of the knob. That points to the thermocouple not making enough mil - Millivolt: pilot on, knob ON, but burner will not light
What I usually find when the pilot is burning, the knob and switch are on and the main burner still won't come on is not the gas valve. It's the littl - Millivolt: pilot will not light with the piezo
If you keep pressing the piezo on your Majestic DVBL7 millivolt fireplace and all you hear is clicks with no pilot, you are probably missing either sp - Pilot and main burner go out while running
Majestic DVBL7 shuts down on its own, pilot and main burner both out. Think vent first. Exhaust coming back into the system starves the flame and trip - Signature Command: no beep after master switch ON
On the Signature Command system, you flip the master switch ON and expect a beep within about 8 seconds. No beep, and nine times out of ten it is the - Signature Command: no spark or no valve click after ON
The Signature Command system beeps, you press ON, and nothing happens at the pilot: no spark, no click from the valve. Before checking anything, turn - Signature Command: pilot lit but main burner will not light
Your pilot lights fine on the Signature Command, but the main burner never comes on. The system uses a sensor on the pilot to prove the flame before i - Signature Command: pilot lockout (green or red-green flash)
The LED flashes every 2 seconds and the fireplace won't start. Green flash means the pilot did not light in the spark time. Red-green means the pilot - Signature Command: sparks but pilot does not light
Signature Command sparks but no pilot. Or sparks once and quits. Spark is in the wrong place, or there is no gas to light. Look at where the spark lan
Napoleon (40)
- Blower noisy, vibrating or rattling
The usual one I find is a dusty blower, especially after drywall work, or a speed switch that is out of calibration and running the motor wrong. The c - Carbon / soot buildup (service flowchart)
Sooting in the firebox - work through altitude, air shutter, venting, orifice and impingement. - Carbon / soot on glass, logs or firebox
Black carbon is being deposited on the glass, logs or combustion chamber. Caused by flame impingement or a blocked air shutter. - Complete unit shutdown - direct vent
Burner (and often pilot) shut down; flame goes blue and see-through before going out - a venting/recirculation fault. - Complete unit shutdown - natural vent / vent-free
Unit shuts down; flame goes blue/ghostly before going out. - Delayed ignition of main burner
Main burner lights late or with a roll-out/puff. - Exhaust fumes smelled in room / occupants get headaches
If you smell exhaust in the room, or anyone is getting headaches while the fireplace runs, stop and shut the unit off first. On a direct-vent Napoleon - Flames always too large or too small / carboning (over- or under-fired)
Flame size is consistently wrong and/or carbon forms. The unit is over-fired or under-fired - check gas pressures. - Main burner flame is blue, lazy and transparent
A lazy, ghostly blue, see-through flame on the GD70 STARfire is a burner that isn't getting enough combustion air, or one that is breathing its own ex - Main burner goes out and pilot goes out
So the main burner and the pilot both go out on you? On the Napoleon GD70 STARfire, that tells you it's most likely a venting issue. If it were just a - Main burner goes out during operation
Main burner shuts off while running. Note flame behaviour first: goes out with no change, goes ghostly blue first, or shrinks after lighting. - Main burner goes out; pilot stays on
Pilot remains lit but main burner drops out - usually low thermopile voltage reaching the valve. - Main burner low flame
Main burner comes on but the flame is smaller than it ought to be, on a Napoleon direct-vent, natural-vent or vent-free unit. Honestly, before you sta - Main burner will not light - direct vent / vent-free
Pilot is on but the main burner will not come on. - Main burner will not light - natural vent
Pilot is on but main burner will not fire on a natural-vent unit. - Odour from fireplace
Smell when the fireplace runs. - Oil-canning (popping/banging metal noise)
Metal pops or bangs as it heats/cools. The sooner after ignition it happens, the closer it is to the heat source. - Pilot drops out during operation - direct vent
Pilot lights fine, then drops out once the unit is running. Direct-vent Napoleon, GD70NT-S and GD70PT-S included. Usually the pilot is sitting wrong, - Pilot drops out during operation - natural vent
Pilot fails while running on a natural-vent unit - often spillage tripping the spill switch. - Pilot drops out during operation - vent-free
Vent-free fireplaces rely on the oxygen depletion sensor (ODS) pilot, so a pilot that fails while the unit is running may just be doing its job. The O - Pilot flame appearance diagnosis and adjustment
The pilot flame tells you a lot if you read it right. On Napoleon fireplaces a correct pilot is steady and blue and covers about 3/8" to 1/2" of the t - Pilot goes out when the gas knob is released
Pilot lights but will not stay lit after the knob is let go. Note: the valve has an interlock that will not let the pilot relight until the thermocoup - Pilot goes out while standing (main burner OFF)
Confirm the gas is shut off at the appliance and the pilot area is clear before you start poking around, and plan on a gas pressure test with a manome - Pilot lit, no gas to main burner (knob on HI, switch/thermostat ON)
Pilot burning, knob on HI, wall switch or thermostat on, and no main flame. Gas valve isn't opening or the call isn't reaching it. Napoleon GD70 STARf - Pilot will not light
No pilot ignition when the piezo push button is pressed. - Pilot will not light (service flowchart)
Step-by-step check when the pilot will not ignite. Same flowchart for direct vent, natural vent and vent-free units. - Pilot will not stay lit - direct vent
Pilot lights but won't hold when you let go of the knob. On a direct-vent Napoleon with a thermocouple, that's most often a thermocouple not making en - Pilot will not stay lit - natural vent
On a Napoleon natural-vent (B-vent) fireplace, the usual thing I find when the pilot won't hold is a weak thermocouple or thermopile signal, or a spil - Pilot will not stay lit - vent-free
Pilot will not hold on a vent-free unit with ODS pilot. - Remote control: blank display or cannot turn fireplace off
Napoleon remote: transmitter display is blank, or it will not shut the fireplace off. Usually batteries or range. Sometimes the receiver is cooking in - Remote control: pairing / code setting and multiple remotes
How to code the hand-held to the receiver; receiver gives a single (possibly faint) beep when it learns the code. - Remote control: receiver will not turn fireplace on, shuts off by itself, or turns on unexpectedly
Receiver-side remote problems. - Test: door gasket seal (paper test)
This is the old paper test for a door gasket on Napoleon gas fireplaces, direct vent, natural vent or vent-free. What I usually find on a call-back is - Test: gas inlet and manifold pressure
This is a procedure for checking gas inlet and manifold pressure on Napoleon millivolt valves. You use it when the burner flame is low, the pilot star - Test: gas valve magnet coil and operator coil
Valve coil resistance / hold-in checks for Robertshaw and SIT 820 Nova valves. - Test: spill switch and wall switch/thermostat wiring
Use this when you need to sort a bad switch from bad wiring, and to confirm the spill switch on a natural-vent Napoleon is intact. Before you touch an - Test: thermocouple and thermopile millivolts
Millivolt test for the generator on a Napoleon gas fireplace. Thermocouple or thermopile. Weak reading means weak pilot or a tired generator. Test, do - Venturi / air shutter adjustment
The venturi (air shutter) sets how much primary air mixes with the gas, and that decides your flame colour. What I usually find is that a fireplace ne - Wall switch OFF but main burner comes on when gas knob turned ON
Wall switch off, gas knob to ON, main burner lights anyway. Napoleon GD70 STARfire direct vent. The switch is not breaking the circuit, so something i - White or grey film on glass, logs or firebox
A white or grey haze builds up on the glass, the logs and the firebox surfaces of the Napoleon GD70 STARfire direct-vent fireplace (GD70NT-S natural g
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.