SIT 820 Nova millivolt valve: main burner will not come on or will not cycle
What is going on
Pilot is fine but the burner will not light with the switch/thermostat, lights intermittently, or the flame looks wrong.
Likely causes
- Knob not on ON, thermostat not calling
- Too much resistance in the millivolt circuit (wire length, thermostat, corroded connections)
- Weak thermo-generator (thermopile)
- Failed main operator
- Wrong orifice, inlet or outlet pressure, partly blocked burner, bad regulator/diaphragm
Check in this order
- Make sure the knob is on ON and the wall switch/thermostat is calling.
- Millivolt circuits are very sensitive to resistance: use a thermostat rated for millivolt, keep connections clean and tight, and keep total thermostat wire length within limits (14 ga 100 ft, 16 ga 64 ft, 18 ga 40 ft, 20 ga 25 ft, 22 ga 16 ft).
- Thermopile test only the thermopile leads on the operator, pilot lit about 3 minutes, TPTH to TP open circuit should be 500-750 mV; adjust the pilot to reach it.
- Closed-circuit jumper TPTH to TH - reading must stay above 300 mV. Then remove the jumper and reconnect the thermostat/switch - must stay above 175 mV (below 150 mV = too much resistance in the thermostat circuit; find and fix it).
- Operator test remove all operator wires and measure resistance TP to TH; out of spec (see SIT table) = replace the valve.
- Burner lights but flame is poor check the regulator matches the fuel, orifice size, inlet and outlet pressure, partial burner blockage; replace the valve if the diaphragm is bad.
Applies to: Fireplaces and gas logs with SIT 820 Nova MV / Millivolt Plus valves
More gas fireplace guides
- Flameworks millivolt valve: pilot outage or burner will not come on
- Maxitrol GV60 remote valve: fireplace will not light or respond
- Proflame (SIT DFC): fan, AUX outlet, split flow or OFF command not working
- Proflame (SIT DFC): pilot lights but main burner will not light or drops out
- Proflame (SIT DFC): pilot will not light or DFC locks out
- SIT 820 Nova millivolt valve: pilot will not light
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SIT 820 Nova MV Troubleshooting Guide; SIT Gas Control Valve troubleshooting flow chart (Fireparts). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.