Napoleon · Gas fireplace troubleshooting

Test: gas inlet and manifold pressure

What is going on

This is a procedure for checking gas inlet and manifold pressure on Napoleon millivolt valves. You use it when the burner flame is low, the pilot starves, or you suspect the supply or regulator is out of spec. Inlet pressure tells you what the house is delivering, and manifold pressure tells you what the valve regulator is passing to the burner. Compare both to the figures below.

Likely causes

  • Burner flame low or lifting and you need to know if supply or valve regulator is at fault
  • Pilot dropping out when the burner lights, suggesting supply starvation
  • After a conversion or valve replacement, to confirm settings
  • Supply or regulator out of spec

Check in this order

  1. Turn the inlet or outlet test screw 2-3 turns counter-clockwise and slip the gauge tube over the fitting
  2. Check inlet pressure with the main burner ON to confirm adequate flow, a reading that falls when the burner lights means supply trouble
  3. Spec (service manual) natural gas supply 7" w.c., manifold 3.5" w.c.; propane supply 11" w.c., manifold 10" w.c. (GD70 manual lists propane inlet 13" normal / 11" minimum)
  4. If inlet is good and manifold is off, the valve regulator is suspect, if inlet is low look upstream at the piping or the regulator
  5. Reseal screws firmly clockwise afterwards, do not over-torque; use a .150" x .030" blade screwdriver
  6. Warning: leak-test the test ports with approved leak solution before leaving, and leave gas adjustments to a licensed technician

Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Testing: Pressures, p.31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.