Napoleon · Gas fireplace troubleshooting
Delayed ignition of main burner
What is going on
Main burner lights late or with a roll-out/puff.
Likely causes
- Pilot too small/mispositioned
- Low supply pressure
- Blocked or wrong-size burner orifice
- Venturi (air shutter) out of adjustment
- Venturi access door leaking (direct vent)
- Burner not level
- Logs out of place
- Embers clogging ports
- Vent or door seal leaks (direct vent)
Check in this order
- Warning: delayed ignition can be hazardous - correct before returning to service.
- Check pilot size and position so it reaches the ignition ports.
- Test inline supply pressure.
- Check burner and orifice for blockage and confirm orifice size is to spec.
- Check and adjust the venturi/air shutter to improve ignition time.
- Direct vent make sure the venturi access door is tightly sealed and its gasket intact.
- Level the burner (direct vent / vent-free).
- Check log position and make sure charcoal/glowing embers are not clogging the ports.
- Direct vent check vent seals and the main door seal for air leaks.
Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Main Burner Delayed Ignition Flowcharts, p.5 / p.14 / p.23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.