Napoleon · Gas fireplace troubleshooting

Complete unit shutdown - direct vent

What is going on

Burner (and often pilot) shut down; flame goes blue and see-through before going out - a venting/recirculation fault.

Likely causes

  • Leaking seals at vent, door, relief doors, burner or pilot
  • Missing 2nd storm collar on vertical terminal
  • Blocked termination
  • Unsealed inner/outer vent joints
  • Vent length/rise outside spec

Check in this order

  1. If the flame does not go blue first, use the Pilot Failure guide instead.
  2. Check seals on vent, main door, relief doors and around the burner and pilot assembly; reseal or replace (use the paper gasket test).
  3. Vertical termination add the 2nd storm collar per the manual diagrams.
  4. Clear any blockage or obstruction at the terminal.
  5. Seal all inner and outer vent pipe joints.
  6. Confirm vent length and rise are within the fireplace and code limits; correct as needed.

Applies to: Napoleon direct-vent gas fireplaces (general service manual flowchart; applies to GD70NT-S/GD70PT-S)

More gas fireplace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Complete Unit Shutdown, p.8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.