Napoleon · Gas fireplace troubleshooting
Blower noisy, vibrating or rattling
What is going on
The usual one I find is a dusty blower, especially after drywall work, or a speed switch that is out of calibration and running the motor wrong. The convection blower on a Napoleon fireplace shouldn't be loud on low. Noise can be a hum, a rattle, a tick or a vibration, and each one points somewhere different. Match the sound to the cause before taking things apart.
Likely causes
- Speed switch out of calibration
- Running on high
- Dirty fins
- Drywall dust in bearings
- Loose mounting or no vibration pad
- Wires touching fins
Check in this order
- Noisy on low recalibrate the variable speed switch, meter on the blower terminals, switch on 'low', turn the calibration screw until it reads 93 volts
- Noisy on high lower the speed
- Clean the fins with a duster, brush or vacuum
- After drywall or construction work, dust may be in the bearings, clean or replace the blower
- Vibrating tighten blower screws and wingnut, and install a vibration pad if the installation instructions call for one
- Ticking or rattling secure harness wires or debris away from the fins
- Turn the power off and let the unit cool before reaching in
Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 4 Other Issues, Blower Flowchart, p.29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.