Napoleon · Gas fireplace troubleshooting
Test: thermocouple and thermopile millivolts
What is going on
Millivolt test for the generator on a Napoleon gas fireplace. Thermocouple or thermopile. Weak reading means weak pilot or a tired generator. Test, do not guess.
Likely causes
- Weak thermocouple or thermopile
- Poor pilot flame not heating the generator properly
Check in this order
- Thermocouple (Robertshaw with adapter, or SIT 820 Nova at the solder button): open circuit should read 20-30 mV, closed circuit 10-15 mV.
- Thermopile open circuit disconnect the leads from terminals 1 and 2, put the meter on mV across the thermopile leads. It should read 500 mV.
- Thermopile closed circuit meter on terminals 1 and 2 with the main burner on. Minimum 150 mV.
- Low readings check the pilot flame first. Clean the pilot and make sure the flame wraps the generator tip.
- Pilot good and still low, replace the generator
Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Testing: Millivolts, p.33-35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.