Napoleon · Gas fireplace troubleshooting
Venturi / air shutter adjustment
What is going on
The venturi (air shutter) sets how much primary air mixes with the gas, and that decides your flame colour. What I usually find is that a fireplace needs the air shutter set a bit different from the factory setting once the vent run, the fuel or the altitude is not what the factory assumed. This is a setup adjustment, not a repair. It matters on the GD70, which leaves the factory set for the longest horizontal run.
Likely causes
- Air shutter not set for vent length, fuel or altitude
- Conversion between natural gas and propane
- Flame too yellow with sooting, or too blue and lifting off the ports
- GD70 installed with a shorter vent run than the factory setting assumes
Check in this order
- Loosen the securing screw and rotate the venturi to open or close
- Closing gives a yellower flame but can cause carboning, opening gives a bluer flame but can lift flames off the ports
- Wait 15-30 minutes for the final flame colour before judging
- GD70 factory set for the longest horizontal run (20 ft), shorter runs need adjustment (propane can go as low as 1/4" open)
- Access by removing the two cover screws on the air housing without damaging the gasket
- Warning: qualified gas installer only, and check the gasket seals again when you put the cover back
Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual); GD70 note from GD70 manual
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Adjustments: Venturi p.44; GD70 W415-0434 Maintenance section. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.