Napoleon · Gas fireplace troubleshooting
Pilot drops out during operation - natural vent
What is going on
Pilot fails while running on a natural-vent unit - often spillage tripping the spill switch.
Likely causes
- Wrong pilot flame
- Pressure drop on burner activation
- Low thermocouple/thermopile output
- Loose connections
- Spill switch tripping or faulty
- Weak magnet coil
- Spillage / negative pressure in room
- Vent outside spec
- Logs out of place
Check in this order
- Check pilot flame size, pattern and position.
- If the pilot shrinks when the burner lights, check pressure drop on activation.
- Test thermocouple and (single-generator systems) thermopile millivolts.
- Tighten connections on thermopile, spill switch and wall switches.
- Test the spill switch function.
- Test the magnet coil.
- Check for spilling test draft at the spill tube and open a window to relieve negative pressure in the room.
- Confirm vent sizing/height meets local code for natural-vent appliances.
- Check log positions.
Applies to: Napoleon natural-vent (B-vent) gas fireplaces with spill switch (general service manual flowchart)
More gas fireplace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 1-3 Troubleshooting, Pilot Failure Flowchart, p.12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.